What Should the Flow Rate Be on My Chiller?Updated 3 days ago

The chiller’s optimal flow range is 5–6+ gal/min. If your flow rate drops below 4.5 gal/min, you may see CLN flash on the screen, indicating that maintenance is needed.

At this time, you should:

If your flow rate is still not within the optimal range after performing maintenance, this may be caused by air entering the system. To correct this, please ensure:

  • All valves and hose connections are hand-tightened fully

  • The filter canister is properly aligned in the grooves of the filter housing and tightened with the filter wrench

  • The inline hose strainer is aligned correctly in its grooves and hand-tightened

Following these steps should restore proper flow and performance.